A cross-connection control program is the set of rules, inspections, backflow preventers and records a water utility uses to stop contaminated water from entering the public supply through customer connections. Building one means adopting legal authority, surveying connections for hazards, requiring the right backflow preventer for each hazard, staffing the program with certified people, enforcing the rules, and keeping records the state can review. Most utilities run these records alongside customer accounts in their water utility management software.

What a Cross-Connection Control Program Includes

A cross-connection is any point where the drinking water system meets a source of contamination, such as a boiler, an irrigation system with fertilizer injection, or a private well. The EPA Cross-Connection Control Manual is the federal reference for these programs, but the requirements come from state rules, and states differ in detail. Wisconsin, for example, requires each municipal water supplier to run a program under NR 810.15, as Madison Water Utility explains.

Every program, whatever the state, covers the same core work:

  • Legal authority: an ordinance, regulation or service agreement that lets the utility require protection and enforce it
  • Hazard evaluation: surveys of new and existing connections to find cross-connections and rate the hazard
  • Backflow protection: the right device for each hazard, installed to code
  • Testing and inspection: proof that each device still works, with records
  • Enforcement and records: steps when customers do not comply, and records the state can review

Two state rules show how this looks in practice. Texas sets requirements in 30 TAC Chapter 290, explained in TCEQ guidance RG-478. Washington lists ten minimum program elements in WAC 246-290-490.

Program elementTexas (TCEQ RG-478)Washington (WAC 246-290-490)
Legal authorityPlumbing ordinance, regulations or service agreementsOrdinance, resolution, code, bylaw or other written legal instrument
Hazard evaluationCustomer-service inspections (CSIs) at set triggersInitial evaluation and periodic reevaluations on a schedule
StaffingLicensed CSI inspectors and backflow testersAt least one certified cross-connection control specialist (CCS)
TestingHealth hazard assemblies tested at installation and at least annuallyApproved preventers inspected or tested under the rule
Quality controlUtility reviews each test report before accepting itWritten test quality control program for testers and reports
IncidentsService may be terminated where an unprotected health hazard is foundWritten backflow incident response procedures
Customer educationGuidance calls education important to every part of the programRequired, for example through bill inserts or new customer notices
Records and reportingTest reports kept at least 3 years; CSI certificates at least 10 yearsAnnual program summary report; records kept up to 5 years

Where should a utility start if it has no written cross-connection control program today?

How to Build a Cross-Connection Control Program

The order matters, because each step depends on the one before it. A utility without legal authority cannot require surveys, and a utility without a hazard list cannot require the right devices. A practical sequence, drawn from TCEQ RG-478 and WAC 246-290-490:

  1. Adopt the legal authority. Pass an ordinance or adopt regulations or service agreements that require backflow protection, give staff the right of entry, and allow enforcement.
  2. Assign qualified staff. Name a program manager and make sure surveys and hazard assessments are done by people with the certification your state requires.
  3. List and survey service connections. Build a master list of connections and inspect new and existing connections to find cross-connections, starting with the highest-risk premises.
  4. Assess the hazard and require the right device. Rate each connection as a high or low hazard and require the backflow preventer your state approves for that rating.
  5. Set testing and report review rules. Require installation and testing of each assembly, and check every test report for tester certification, gauge calibration and completeness.
  6. Write enforcement and incident procedures. Define deadlines, notices, service shutoff and who to notify, plus the steps to follow if a backflow incident happens.
  7. Educate customers and report to the state. Tell customers why the program exists, keep the required records, and file any annual summary or incident report your state requires.

Steps 1 to 3 are usually the slowest. A utility starting from scratch may survey only commercial and industrial connections in the first year, then work through irrigation and residential accounts with known hazards.

Setting the Legal Authority

Legal authority is the first element in both states. TCEQ RG-478 says every Texas public water system must adopt a plumbing ordinance, plumbing regulations, or service agreements, and that the document must include three critical elements:

Right of entry. Staff and inspectors need authority to enter facilities to evaluate cross-connections, backflow risks and plumbing materials.

Lead ban. The document must prohibit plumbing materials with lead above federal standards.

Enforcement. The utility needs the power to set fees and due dates, require installation, and discontinue water service.

Ownership decides which document a utility uses. Cities and districts usually adopt ordinances. RG-478 notes that most public water systems do not have the governmental structure to adopt ordinances, so they use customer service agreements instead. Investor-owned utilities in Texas have limited authority to adopt rules stricter than TCEQ's and need TCEQ approval to do so.

Local rules can be stricter than the state's but not weaker. RG-478 also points out that adopting a plumbing code is not the same as having program authority: plumbing codes cover design and installation, but not enforcement. For how Texas divides drinking water, rate and service area oversight among its regulators, see the Texas water utility regulations guide.

Hazard Surveys: How Utilities Find Cross-Connections

Surveys are the foundation of the program. RG-478 calls customer-service inspections the foundation of a successful program and requires one for all new construction, for existing connections where the utility has reason to believe a hazard exists, and for existing connections after a material change to the private plumbing. Washington requires an evaluation before service begins for connections made on or after April 9, 1999, and periodic reevaluations on an approved schedule and whenever the use of the premises changes.

The survey also decides where protection goes. There are two approaches, and many programs use both:

ApproachWhere the protection isBenefitLimitation
Containment (premises isolation)One assembly at the service connection or meterProtects the public supply with a single assemblyPeople inside the building remain exposed to internal hazards
Internal protection (in-premises)Assemblies at each hazard inside the buildingProtects the public supply and the building's own occupantsMore assemblies to track, and internal changes can go unnoticed between surveys

Texas allows a site with an adequate internal program to skip protection at the meter, but only if every health hazard assembly inside is tested each year by a licensed tester and the utility keeps the reports. RG-478 recommends periodic surveys for these sites, since internal plumbing can change without the utility knowing.

Matching Hazard Levels to Backflow Preventers

Once the survey rates a connection, the program sets which device is acceptable. Washington's rule gives a clear example in its table of approved methods for premises isolation, summarized here from WAC 246-290-490:

Degree of hazardApproved backflow preventer for premises isolation
Severe health hazard (wastewater treatment plants, radioactive material processing, nuclear reactors)Approved air gap, or a reduced pressure assembly combined with an in-plant air gap
High health hazardAir gap, reduced pressure backflow assembly (RPBA) or reduced pressure detector assembly (RPDA)
Low hazardAir gap, RPBA, RPDA, double check valve assembly (DCVA) or double check detector assembly (DCDA)

The same rule lists premises that pose a high health hazard and need premises isolation by an air gap or reduced pressure assembly. Examples include:

  • Hospitals, medical and dental clinics, and nursing homes
  • Car washes
  • Chemical plants
  • Commercial laundries and dry cleaners
  • Food processing and beverage bottling plants
  • Laboratories and metal plating industries
  • Mortuaries
  • Irrigation systems on the utility's supply with chemical addition

A utility can grant an exception if its specialist finds no hazard at a listed premises, but Washington requires that decision to be documented case by case. Texas works the same way: RG-478 gives the example of a dental clinic where a survey found no connection to the potable supply, so backflow prevention may not be required.

Who Runs the Program: Staffing and Certification

A program needs at least one person who owns it, and most states set certification rules for the people doing surveys and tests. In Washington, the program must include at least one person certified as a cross-connection control specialist (CCS), and a CCS must assess the degree of hazard and decide the method of protection for each connection. The Washington water utility regulations guide covers the state's wider drinking water framework.

Texas spreads the work across licenses. A CSI can be done by a TCEQ-licensed customer-service inspector, a plumbing inspector, or a licensed plumber with a water supply protection specialist endorsement. Testing is done by licensed backflow prevention assembly testers.

The program manager rarely works alone. RG-478 suggests involving:

  • Utility or district management responsible for the program
  • A plumbing inspector or building official
  • Permitting staff who see new hazards first
  • The fire marshal's office, for fire suppression systems
  • Administrative staff who receive customer calls and review forms
  • Local plumbers, irrigators, testers and inspectors who work under the utility's rules

Washington also lets a utility run all or part of its program through a contract with another agency or party the state accepts, which helps small systems without a certified specialist on staff.

Does your ordinance say who can shut off water for a cross-connection, and who has to be told first?

Enforcement and Service Shutoff

Without enforcement, a program has rules but no way to apply them. Washington requires corrective action when a cross-connection is not controlled or a customer fails to install, test, maintain or repair a required preventer. Under WAC 246-290-490, that action may include denying or discontinuing service until the hazard is controlled, requiring the customer to install a preventer, or the utility installing one itself. Except in an emergency, the utility must notify the local authority having jurisdiction before it shuts off service.

Texas guidance is similar. RG-478 says a utility may terminate service where an unprotected health hazard is found and restore it only once the hazard is removed or isolated. Madison Water Utility notes that repeated failure to perform or report the annual test can lead to a citation.

Most programs use a ladder of steps: a first notice with a deadline, a second notice, a final notice that names the shutoff date, then shutoff and restoration once the customer complies. Each step is a dated task with an owner, which is why many utilities track enforcement through the same system they use for field work. The guide to work order management for water utilities covers how those tasks are assigned and closed.

Records and State Reporting

Records show the program is working. Washington requires a master list of connections where the utility relies on a backflow preventer, with the hazard level and required device for each, plus an inventory of every preventer with its location, type, manufacturer, model, size, serial number, installation date and test history.

RecordWhat it holdsHow long to keep it
Master list of protected connections (Washington)Each premises, its hazard level and required preventerAs long as the premises poses a hazard
Backflow preventer inventory (Washington)Location, description, hazard, installation date, inspections, tests and repairs5 years or the life of the preventer, whichever is shorter
Incident reports and annual summary (Washington)Backflow incidents and the yearly program summary report5 years
Test and maintenance reports (Texas)Signed tester reports for each assemblyAt least 3 years
Customer-service inspection certificates (Texas)Survey results for each connectionAt least 10 years, or as a permanent record

Reporting deadlines can be short. Washington requires a utility to notify the state, the local authority and the local health jurisdiction by the end of the next business day when it learns of a backflow incident that contaminated the public system or occurred on a customer's premises.

Could your team produce the hazard level, device and last test date for any protected connection within a few minutes?

These records sit alongside the rest of a utility's compliance work, which the guide to water utility compliance software covers in more detail.

Where SMART360 Fits

A cross-connection program depends on records tied to the right property: the service location, the customer, the assets at that location and the work done there. When those records live in separate spreadsheets, a new owner or a new connection can be missed.

SMART360 by Bynry is a cloud platform for water, electric and gas utilities serving 3,000 to 100,000 accounts. It keeps customer accounts, service locations, assets, work orders and customer notices in one system, so staff can see a property's records and open follow-up work without moving between tools. More than 50,000 accounts are live on the platform, customer retention is 95%, the service runs under a 99.9% uptime SLA, and SMART360 is SOC 2 certified. A typical go-live takes 20 to 24 weeks.

Conclusion

A cross-connection control program protects the public water supply by finding every connection to a hazard and making sure the right backflow preventer stays in place. The work follows a set order: legal authority, qualified staff, surveys, hazard ratings and device requirements, testing and report review, enforcement, and records. State rules such as Texas 30 TAC 290 and Washington WAC 246-290-490 set the minimums, and local rules can go further. The program runs on accurate records for every protected connection, so the system that holds them matters as much as the rules.

See SMART360 in Action

SMART360 keeps accounts, service locations, assets and work orders together, so cross-connection follow-up sits with the rest of the customer record. See SMART360 water utility management software and how it brings field work and account records into one place.

Frequently Asked Questions

What is a cross-connection control program?

A cross-connection control program is the set of rules, surveys, backflow preventers, tests and records a water utility uses to keep contamination from flowing back into the public water supply through customer connections. State drinking water rules require one, and local ordinances or service agreements give the utility authority to enforce it.

Who is required to have a cross-connection control program?

State rules decide. Texas requires public water systems to adopt cross-connection control requirements under 30 TAC 290, Washington requires every community water system to comply with WAC 246-290-490, and Wisconsin requires municipal suppliers to run a program under NR 810.15.

What is a cross connection control specialist?

A cross connection control specialist (CCS) is a certified person who assesses the hazard at each connection and decides the method of backflow protection. Washington requires every program to include at least one certified CCS. Other states use different titles, such as customer-service inspector in Texas.

What happens if a customer does not install or test a required backflow preventer?

The utility follows the enforcement steps in its ordinance or service agreement, usually notices with deadlines, then shutoff of water service until the hazard is controlled. In Washington the utility must notify the local authority before shutting off service, except in an emergency.

How long should cross-connection records be kept?

It depends on the state. Texas requires backflow test reports to be kept at least three years and customer-service inspection certificates at least ten years. Washington requires most program records and annual summary reports to be kept for five years.